Harmonic Filter Reactors

Reactors: We manufacture Iron Core & Air Core Reactors as per IS 5553.

Application: Used with harmonic filter duty power capacitors to mitigate Harmonics, improve power factor and avoid electrical network.

Design and construction: Reactors are designed for 20% overload continuously And which will not saturate at 150% of rated current. They are designed for continuous Operation in an ambient temp 60° C with natural air cooling. Temp. Class as 'F'. Reactors are fitting with thermal overload protector in one coll.

  •   Core is made out of best stamping with very low core loss.
  •   Coll are made with SE/DFG Copper Strip Class 'F'.

  •   Interlayer insulation by Nomex paper.
  •   Inductors are vacuum impregnated with F class varnish
           followed by over pressure (VPI).
  •   Frame parts Zinc Plated.

  •   Termination on nickel plated studs.
  •   Tie rods are provided for mechanical strength and avoid
           vibration / noise.
Standards IEC 60289/VDE 0532/En61558/IS 5553
Rated Voltage and Frequency Un = 440V, 50 Hz
Series Resonance Frequency 210Hz (5.67%), 189Hz (7%) and 134Hz (14%)
Duty Cycle (Irms) 100%
Class of Protection IPOO
Ambient Temperature 50° C
Temperature Class Class 'F'
Protection T.O.P.